Three phase motor loading chart.

The following table shows the load current drawn by three phase motors of various power ratings and supply voltages. To read this table, look up the power of your motor in the either of the yellow columns and then read along to the appropriate voltage current. The value indicated is the full load current in amps.

Power

Current in Amps at indicated voltage

KW

HP

220V

240V

380V

 415V

440V

0.75

1

3.6

3.3

2.1

1.9

1.8

1.1

1.5

4.7

4.3

2.7

2.5

2.4

1.5

2

6.4

5.9

3.7

3.4

3

2.2

3

9.1

8.3

5.3

4.8

4.6

3

4

12.1

11

7

6.4

6.1

3.7

5

14.6

13.4

8.5

7.8

7.3

5.5

7.5

21.8

20

12.6

11.6

10.9

7.5

10

27.2

25

15.8

14.4

13.6

9.32

12.5

32.6

30.1

18.9

17.3

16.3

11

15

39.7

36.5

23

21.1

19.9

15

20

52

48

31

28

26

18.5

25

66

60

38

35

33

22

20

78

72

45

41

39

25

35

92

84

53

48

46

30

40

105

96

61

55

52

33

45

118

108

68

62

59

37

50

131

120

76

69

65

45

60

157

144

91

83

78

51

70

183

168

106

97

91

59

80

207

190

120

110

104

67

90

232

212

135

123

116

75

100

258

235

149

136

129

90

125

317

290

188

171

158

110

150

377

345

218

200

188

129

175

436

403

252

231

218

147

200

496

454

288

263

248

168

225

---

---

320

293

276

185

259

---

---

354

324

306

220

300

---

---

420

385

363

257

350

---

---

490

449

424

295

400

---

---

546

505

473